Skip to tool
ecech.
🏠 Home & Construction

The Ampacity Table Says 12 AWG and the Distance Says 8

A 20 amp circuit 100 feet away drops 6.6% on 12 AWG. Sizing by amps alone is how a long run ends up dim and a pump motor dies young.

For planning only. Voltage drop is one input to circuit design. Conductor type, ambient temperature, bundling, conduit fill, breaker coordination and local code all matter and are not covered here. Have the circuit designed and installed by a licensed electrician.

Voltage drop

 

Voltage at the load

Smallest compliant gauge

 

Max length on your gauge

to stay inside the limit

Every gauge on this run

The calculation

Advertisement

How the calculation works

20 A, 100 ft one way, 120 V copper — drop as a percentage 3% limit 14 AWG 10.46% 12 AWG 6.58% 10 AWG 4.14% 8 AWG 2.60% — passes Bars are 35 px per percentage point. The ampacity table allows 12 AWG here; the distance does not.

How to Use This Tool

Enter the load, the one-way run length and the gauge you were planning to use. The tool reports the drop and then finds the smallest conductor that stays inside the limit.

Two different questions, two different answers

Ampacity asks whether the conductor will overheat. That is a question about current alone, and it is what wire size charts answer: 14 AWG for 15 A, 12 AWG for 20 A, 10 AWG for 30 A.

Voltage drop asks whether enough voltage arrives at the far end. That depends on current times length, so a short 20 A run and a long 20 A run need different conductors. Both questions have to pass, and on runs over about 50 feet the second one usually decides.

VD = 2 x K x A x L / CM

14 AWG   2 x 12.9 x 20 x 100 /  4,110 = 12.55 V = 10.46%
12 AWG   2 x 12.9 x 20 x 100 /  6,530 =  7.90 V =  6.58%
10 AWG   2 x 12.9 x 20 x 100 / 10,380 =  4.97 V =  4.14%
 8 AWG   2 x 12.9 x 20 x 100 / 16,510 =  3.13 V =  2.60%  passes
20 A, 100 ft one way, 120 V, copper, 3 per cent limit

Where the formula comes from

The 2 is the round trip: current flows out along one conductor and back along the other, so the resistive length is twice the run. K is the resistivity of the metal expressed in ohm-circular-mils per foot, 12.9 for copper and 21.2 for aluminium. CM is the conductor's cross-sectional area in circular mils, which is what AWG numbers actually encode.

Because CM roughly doubles every three gauge sizes, dropping three sizes halves the voltage drop. That is a more useful mental model than memorising a table.

Why undersizing kills motors rather than tripping breakers

A resistive load at reduced voltage simply produces less heat or light. A motor is different: it draws more current to deliver the same mechanical power, and that extra current heats the windings. A well pump, compressor or workshop tool at the end of a long undersized run runs hot for years and then fails, with no breaker trip to point at the cause.

Low voltage is where this bites hardest

The limit is a percentage, and on 12 V systems 3 per cent is only 0.36 V. Landscape lighting, solar and automotive runs therefore need conductors that look absurdly large for the current, which is why a 12 V LED path light 60 feet from the transformer often needs 10 AWG for a couple of amps.

Aluminium needs two sizes up

Aluminium's resistivity is about 1.64 times copper's, so for the same drop it needs roughly two AWG sizes larger. It also requires different terminations and antioxidant compound, so it is not a substitution to make casually on an existing circuit.

The 3 per cent figure is a recommendation

In the NEC, voltage drop appears in informational notes rather than as a mandatory limit: 3 per cent on a branch circuit and 5 per cent total including the feeder. Some jurisdictions adopt it as a requirement. Treat it as good practice and confirm locally.

Advertisement

Frequently Asked Questions

What wire size do I need for a 20 amp circuit 100 feet away?
For heat alone, 12 AWG. For voltage drop on 120 V, 12 AWG gives 6.58 per cent, which is over the 3 per cent recommendation, so 8 AWG is the smallest conductor that passes at 2.60 per cent.
How do you calculate voltage drop?
VD equals 2 x K x amps x one-way length divided by circular mils. K is 12.9 for copper and 21.2 for aluminium. The 2 accounts for current flowing out and back, which is the part most often left out.
Is 3 per cent voltage drop a code requirement?
In the NEC it appears in informational notes rather than as a mandatory rule: 3 per cent on a branch circuit and 5 per cent total. Some local jurisdictions adopt it as a requirement, so confirm locally rather than assuming.
What happens if voltage drop is too high?
Resistive loads underperform quietly. Motors are the real problem: they draw more current at reduced voltage to produce the same power, which overheats the windings and shortens life without ever tripping a breaker.
Why does 12 volt wiring need such thick wire?
Because the limit is a percentage of a small number. Three per cent of 12 V is 0.36 V, so a landscape lighting run of 60 feet can need 10 AWG for only two amps, where the same current on 120 V would be fine on 14 AWG.
Can I use aluminium instead of copper?
Only with the right terminations, and two AWG sizes larger for the same voltage drop, because aluminium's resistivity is about 1.64 times copper's. Mixing metals at a terminal is a known failure mode, so this is a job for an electrician.

Related tools in Home & Construction

Browse all Home & Construction tools
The person who builds ecech., at the desk where the tools are written.

Made by one person

ecech. is not a content farm. Every tool here is written and checked by hand, one at a time, by someone who wanted the tool to exist and could not find a version that showed its working.

No accounts and no sign-in, and nothing you type reaches a server — every calculation on this page runs inside your browser. The ads are served by Google and do set their own cookies, which is set out in full on the privacy page. More about the site.